| Application/Usage Area | Conductors ESD Grade Carpet Tile | Shadow FX MC Carpet Tile | ESD Vinyl Tile (Conductive) | Dissipative SDT Vinyl Tile | ESD Epoxy (Conductive)** | Eclipse EC Rubber Tile and Sheet |
|---|---|---|---|---|---|---|
| Mission-Critical Data Centers and Networked Offices | NR* | Ideal | NR | NR | NR | Ideal |
| Mission-Critical Government & NOC | NR* | Ideal | NR | NR | NR | Ideal |
| Electronics Manufacturing ANSI/ESD S20.20 | R | R | Ideal | NR | R | Ideal (Meets Class-0)*** |
| Offices Inside Electronics Manufacturing or Testing | Ideal | Ideal | R | NR | R | Ideal |
| Engineering Areas in EPAs | Ideal | Ideal | Ideal | NR | R | Ideal |
| R&D & Laboratories | NR* | Ideal | R | NR | NR | Ideal |
| 911 Applications | NR* | Ideal | NR | NR | NR | Ideal |
| Command Centers | NR* | Ideal | NR | NR | NR | Ideal |
| FAA STD 019 Flight Control | NR* | Ideal | NR | NR | NR | Ideal |
| Clean Rooms | NR | NR | R | NR | R | Ideal |
| Hospital/MRI | NR* | Ideal | NR | NR | NR | Ideal |
Ideal = Highly Recommended
R = Recommended
NR = Not Recommended
* ESD grade carpet tile is not recommended for use in FAA flight areas, data centers, 911 dispatch areas, or communication rooms because it is too conductive. ESD grade carpet tile can measure as low as 2.5 X 10 E4. ESD grade carpet tile with conductive recycled backing does not meet the minimum resistance limits of FAA STD 019e, IEEE 1100-2005, Motorola R56 or ATIS-0600321-2010. Before specifying ESD grade carpet tile in these applications Staticworx recommends reviewing the appropriate grounding standards with a technical resource.
** Static Dissipative Epoxy does not meet the kV rating limits of ANSI/ESD S20.20 in all the applications shown above.
*** Eclipse EC Rubber is the only ESD flooring certified as Class-0 Qualified.
Request Your Free ESD Flooring DVD
Get your copy of
"Flooring that Keeps You Grounded" DVD
with all the ESDTile.com videos featuring Dave Long.
Staticworx Launches First Anti-Static Carpet to Meet Safety Standards for Use Around Electricity
Shadow FX “Covers It All”:
Accents Safety, Aesthetics, Savings, and Sustainability

Knowledge is Power
Dave Long, president and CEO of Staticworx, has 35-plus years of industry experience & widely recognized as the foremost authority on electrostatic discharge (ESD) flooring...
View the Ground Wire Archives