Choose ESD Flooring by Application

Rating Different ESD Flooring applications

are you grounded?

View PDF Rating Different ESD flooring applications

Application/Usage Area Conductors ESD Grade Carpet Tile Shadow FX MC Carpet Tile ESD Vinyl Tile (Conductive) Dissipative SDT Vinyl Tile ESD Epoxy (Conductive)** Eclipse EC Rubber Tile and Sheet
Mission-Critical Data Centers and Networked Offices NR* Ideal NR NR NR Ideal
Mission-Critical Government & NOC NR* Ideal NR NR NR Ideal
Electronics Manufacturing ANSI/ESD S20.20 R R Ideal NR R Ideal
(Meets Class-0)***
Offices Inside Electronics Manufacturing or Testing Ideal Ideal R NR R Ideal
Engineering Areas in EPAs Ideal Ideal Ideal NR R Ideal
R&D & Laboratories NR* Ideal R NR NR Ideal
911 Applications NR* Ideal NR NR NR Ideal
Command Centers NR* Ideal NR NR NR Ideal
FAA STD 019 Flight Control NR* Ideal NR NR NR Ideal
Clean Rooms NR NR R NR R Ideal
Hospital/MRI NR* Ideal NR NR NR Ideal

Ideal = Highly Recommended
R = Recommended
NR = Not Recommended

* ESD grade carpet tile is not recommended for use in FAA flight areas, data centers, 911 dispatch areas, or communication rooms because it is too conductive. ESD grade carpet tile can measure as low as 2.5 X 10 E4. ESD grade carpet tile with conductive recycled backing does not meet the minimum resistance limits of FAA STD 019e, IEEE 1100-2005, Motorola R56 or ATIS-0600321-2010. Before specifying ESD grade carpet tile in these applications Staticworx recommends reviewing the appropriate grounding standards with a technical resource.

** Static Dissipative Epoxy does not meet the kV rating limits of ANSI/ESD S20.20 in all the applications shown above.

*** Eclipse EC Rubber is the only ESD flooring certified as Class-0 Qualified.

Flooring that Keeps you Grounded DVDRequest Your Free ESD Flooring DVD

Get your copy of

"Flooring that Keeps You Grounded" DVD

with all the ESDTile.com videos featuring Dave Long.

Request a Free DVD Now!